Midas
®
Gas Detector
7-8
13. Use the ‘s’ up or t down buttons to change
the A2 value.
14. Press 3 to display the flashing alarm on time
delay (seconds).
15. Use the ‘s’ up or t down buttons to change
the alarm on time delay (seconds).
16. Press 3 to display the flashing alarm output
latching (L) or non latching (nL) setting.
17. Use the ‘s’ up or t down buttons to change
between the settings.
18. Press 3 to display the flashing alarm relays
normally energized (nE) or normally de-energized
(nd) setting.
19. Use the ‘s’ up or t down buttons to change
between the settings.
20. Press 3 to update all the changes (UPdt
displayed) and return to step 1.
21. Press ‘s’ up or t down to select another
submenu.
22. Press ‘X’ to return to set-up, calibration and test
menu selection.
23. Press ‘X’ again to return to normal operation.
Note
When replacing a single gas sensor cartridge
with the same type single gas sensor cartridge,
no change of gas conrmation is required.
When changing a multi gas sensor cartridge
with the same type multi gas sensor cartridge,
the new sensor cartridge will assume
the same previously set gas ID and will
not request a change gas conrmation. See
Appendix B for cartridge information.