the Midas
®
reports an “F81” (Flow Fail) –
approximate time to fault is 1 minute
10. Remove the plug
11. Allow 15 seconds or so to allow the Midas
®
flow
and concentrations to stabilize then clear the
fault by pressing and holding ‘X’
12. Return the unit to normal operation
Diagram 8-8. Port Location.
Gas outlet port
Gas inlet port