9 SLA Alarm Scenarios
SLA Battery alarm functionality under few scenarios are detailed below. Note these item parameters to
understand the alarm behavior in detail.
ITEM NUMBER DESCRIPTION OPTIONS/RANGE
1607 SLA Not Charging Alarm Days 0-255 days (0 means alarm will be disabled)
1608 SLA Not Charging Alarm Active/Inactive
1614 SLA Not charging alarm counter in days
Scenario 1: SOLAR PANEL REPLACEMENT
Example:
At T1 i1607 is configured as 10 (days). After 10 days of SLA not charging, alarm raises at T2.
At T3, if the solar panel is replaced after 5 days from T2 user has to reset the alarm i1608 so as to restart
the battery monitoring from T3. Then, the device auto resets the alarm counter i1614 (value=0) .
At T4, alarm raises if SLA battery is not charging after 10 days (i1607 configured value).
Scenario 2: REGULAR MAINTENANCE (OR WHEN SOLAR PANEL LOST/STOLEN)
Example:
At T1 i1607 is configured as 10 (days).
Within 10 days at T2 if the solar panel is replaced then, the user has to first reset alarm counter i1614
(value=0). This will enable the device to restart the battery voltage monitoring for the alarm from T2 and
this indicates to the device that an external user action (panel replacement) has happened.
At T3, alarm raises if SLA battery is not charging after 10 days (i1607 configured value) from T2.
9 SLA Alarm Scenarios