AMPS-24 Manual — P/N 51907:J2 02/26/2014 35
Programming the AMPS-24 Configuring the AMPS-24
The worksheet’s summary section displays all selections. When programming is complete, PK-PPS
displays the SLC address consumption that is the result of your selections.
Figure 3.4 PK-PPS: Label
Label
For greater ease of identification, you may create a label for each power supply. Labels may have a
maximum of 40 characters.
Figure 3.5 PK-PPS: Battery Charger/Outputs Current Setup
Outputs Current Settings
Choose the appropriate battery charger current for the system’s battery capacity. Refer to
Section 4.2, “Calculating the Battery Requirements”, on page 44 for more information on
determining your system’s battery capacity.
There are three charger current options. Select
1A CHARGE for 7 to 26AH, 2A CHARGE to charge 12
to 26 AH batteries. Select
5A CHARGE to charge 55 to 200 AH batteries. Select DISABLE CHARGER
when the batteries will be charged by an external charger (See “Setting the Charger” on page 26.).
NOTE: The charger current option “1A CHARGE” is not approved for ULC applications.