38 AMPS-24 Manual — P/N 51907:J2 02/26/2014
Configuring the AMPS-24 Configuring the FACP
switch selection and in the order given in Table 3.3. Each SLC address may also be programmed
manually at the panel or through the VeriFire Tools utility. Note that either one or five addresses
can be associated with the power supply depending on the configuration.
3.4.2 Software Type ID Codes
When manually programming AMPS-24, each address point on the AMPS-24 should carry the
module type, “MONITOR”; the Type Code Label, “POWER MONITR”; and the FlashScan Code
Label “PS MON.” Refer to the panel programming manual or VeriFire Tools Online Help for
further instructions.
3.4.3 Panel Display
When the power supply is configured for Five Point Monitoring, a specific trouble message for
each AMPS-24 address will display. Five Point Monitoring must be selected for proper AC Fail
reporting. See Section 3.1 for further information.
Order of AMPS-24
Address Assignment
AMPS-24 Addresses Type ID
FlashScan Code
Label
B
*
Monitor General POWER MONITR PS MON
B+1 Monitor AC Fail POWER MONITR PS MON
B+2 Monitor Battery POWER MONITR PS MON
B+3 Monitor Earth Fault POWER MONITR PS MON
B + 4 Monitor Charger Fault POWER MONITR PS MON
Table 3.3 Addressing
* B = Base Address
NOTE: AMPS-24/E revisions previous to the AMPS-K2 revision do not have the extra monitor
point for Charger Fault. When replacing a previous revision AMPS-24 with an AMPS-K2 version,
remember to program the monitor point.
!
CAUTION:
SLC Trouble Reporting must be selected when an AMPS-24 is connected to an NFS2-3030.