Controls:
Dedicated flush
pushbuttons are provided
for the following functions: MUTE BUZZER, EXTEND DELAY,
END DELAY/EVACUATE, SILENCE/
RESOUND, RESET,
Additional pushbuttons for
configuration and selection
of software functions:
2
4
6
8
KEYS
5
KEY
0..9
KEY
KEY
10 BUTTON NUMERIC KEYPAD
System Capacity:
Number of loops: 1
Number of zones: 32 (16 Fire + 16 Plant Alarm)
Devices per loop: CLIP or OPAL* protocol: 99 sensors
+ 99 modules or 99 sensors +
combination of up to 99 modules/
sounders within strict limits.
External Connections:
Cable entry: 16 x 20mm knock-outs in top of cabinet.
Terminals: All external connections made
through screw terminals, each of
which will accept cable sizes
between 0.5mm
2
and 2.5mm
2
.
Electrical:
Classification: Installation Class 1, (panel must be
earthed).
Power Supply and Charger
Operating Voltage: 230V 50Hz AC
Voltage Tolerance: +10% -15%
Base card input: 18V AC from integral mains
transformer.
Battery Charger output: 27.1V nom. @ 20ºC (temperature
compensated and current limited).
AUX DC Output Voltage: Maximum output voltage = 29V
1
Minimum output voltage = 17.1V
2
.
EN54 Battery Wiring Test Impedance: 0.4 Ohm
EN54-4 PSU Loadings:
I
max(a)
= 350mA @26.0Vdc
I
max(b)
= 2.1A @26.0Vdc
1 At maximum AC mains voltage (230V +10%)
2 At V
IN
= 196 VAC and with panel fully loaded.
* Loops can be configured to poll CLIP
devices or, when OPAL protocol is
enabled, a mixture of OPAL and CLIP
devices, providing no more than 10
CLIP devices are configured.