ID50 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 1 - Specifications
A1 - 3 997-263-000-11, Issue 11
January 2010
Fuses:
The location of the panel fuses is given here, together with their
ratings and their type.
a. MF1 Mains Supply T 2A H 250V
b. FT1 Transformer secondary T 5A H 250V
c. FC1 Battery T 3.15A H 250V
T = time delay (i.e. anti-surge), H = high break capacity, as
defined by EN 60127.
Note: Fuses FT1 and FC1 refer to main PCB version 8,
or later, or P/N: 124-390. These were previously
labelled FS1 and FS2, repectively.
Panel Quiescent Current
3
: 110mA
Panel Alarm Current
4
: 140mA
Battery Charging Current
5
: 0.63A (max.)
0.47A (min.)
0.50A (nom.)
AUX DC Output
6
: 0.25A
PSU Output Rating (continuous): 2.5A
Ripple Voltage (p/p.): 1.5V @ 1.5A load
Standby Batteries: 12Ah (max.)
Outputs:
a. Two dedicated Monitored Sounder Outputs.
b. Two Sounder or Volt-free Contact (VFC) - selectable outputs.
c. Two Switched -VE Outputs (RLY) - unselectable outputs.
d. One loop output.
e. One DC auxiliary output.
Sounder Output Rating
Type: Voltage reversal.
Output voltage: 16.6 to 30V (when active)
Maximum load: 1A Total (max. 700mA per output).
Fuse rating: Electronic over-current protection.
Monitoring: Open- and short-circuit with resistor
EOL device. Partial-open-and -
short circuit with diode EOL device
fitted.
3 Back light off
4 Back light on, fire relay and two sounder relays on.
5 Battery charger output is disconnected in alarm.
6 Total AUX DC power available - split axross both AUX and FBF output (VdS only).