ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
87 997-263-000-11, Issue 11
January 2010
5.7.5 Interrupt Delay
The Interrupt Delay option has two settings, Yes (Y) or
No (N). This option is only available with the Fire rule.
Caution: Selecting ‘No’ contravenes the
requirements of EN54.
To change the Interrupt setting from the CBE Output
Rules menu:
1 Press the ‘
5
button using the numeric keypad to
select the Interrupt option.
2 Press the ‘
6
’ button to select the required setting.
Refer to Section 5.7, Control-by-Event Output
Rules for further information.
3 Confirm the selection by pressing the ‘
5
button. To
cancel the selection, press ‘
4
’. In either case the
menu below is re-displayed.
5.7.6 Class Change
This control parameter has two options, Yes (Y) and No
(N). These indicate whether or not the selected CBE
Rule’s assigned outputs activate when Digital Input 1 is
configured as Class Change and then operated. To
configure Class Change, from the CBE Output Rules menu:
1 Press the ‘
6
button using the numeric keypad to
select the Class Change option.
2 Press the ‘
6
’ button to select the required setting.
Refer to Section 5.7, Control-by-Event Output
Rules for further information.
3 Confirm the selection by pressing the ‘
5
button. To
cancel the selection, press ‘
4
’. In either case the
menu below is re-displayed.
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
CBE Rule:01 Interrupt = [N]
>:Change :Accept < : Cancel
CBE Rule:01 Interrupt = [Y]
>:Change :Accept < : Cancel
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
CBE Rule:01 6:Class Change 7:Two Zone
9:Zones ¦ : More
CBE Rule:01 Class Change = [N]
> : Change : Accept < : Cancel
CBE Rule:01 Class Change = [Y]
> : Change : Accept < : Cancel
CBE Rule:01 6:Class Change 7:Two Zone
9:Zones ¦ : More
6
5
5
6
5
6
EN54-2 : 7.11.d.
Configured delays MUST
be set to interruptable
(Y) to remain EN54
compliant.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals