ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
44
997-263-000-11, Issue 11
January 2010
[Setup] Automatic Resound = ANY ZONE
> : Change ¦ : More < : Exit
3 Press the ‘
6
’ button to select the required setting,
either ON or OFF.
4 Press ‘
4
to return to the Setup menu. All changes
will be saved on exiting this menu.
5.5.1.9 VdS Compatibility
The VdS Compatibility option must be set to ‘Disabled’.
1 From the Setup menu, using the numeric keypad
press the ‘
1
’ button to enter the Panel Options
menu.The Language screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options until the ‘VdS Compatibility’ menu is displayed.
3 If necessary, press the ‘
6
button to change VdS
Compatibility from ‘ENABLED’ to ‘DISABLED’. Press
4
to return to the Setup menu. All changes will be
saved on exiting this menu.
5.5.1.10Automatic Resound
By default, after the panel has received a fire event and
the sounders have been silenced using the SILENCE/
RESOUND pushbutton a new fire event, in ANY zone,
will re-activate the sounder outputs. This option allows
the configuration of sounder outputs either to re-activate
with NEW zone-in-fire events or ignore any new fire
events after the sounders have been silenced.
1 From the Setup menu, using the numeric keypad
press the ‘
1
’ button to enter the Panel Options menu.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options until the ‘Automatic Resound’ menu is displayed.
3 Press the ‘
6
’ button to select the required setting, either
NEW ZONE or NO. Press ‘
4
’ to return to the Setup menu.
All changes will be saved on exiting this menu.
1
or
8
2
6
[Setup] Language = English
> : Change ¦ : More < : Exit
[Setup] VdS Compatibility = DISABLED
> : Change ¦ : More < : Exit
6
or
8
2
[Setup] Diagnostic Mode = ON
> : Change ¦ : More < : Exit
[Setup] Diagnostic Mode = OFF
> : Change ¦ : More < : Exit
[Setup] Automatic Resound = NEW ZONE
> : Change ¦ : More < : Exit
[Setup] Automatic Resound = NO
> : Change ¦ : More < : Exit
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals