EasyManua.ls Logo

Honeywell NOTIFIER LDM-32 - UL Power-Limited Wiring Requirements

Honeywell NOTIFIER LDM-32
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
Wiring Considerations Supervision Input - TB1, Terminals 6 & 7
4.7 Supervision Input - TB1, Terminals 6 & 7
The Supervision Input, which requires a normally-closed condition, can be used for supervising power sources or other devices. It must
be power-limited. If employed, a change in status will be transmitted to the host control panel in the event of device failure or restoral. If
not used, a jumper must be installed across these terminals on TB1. A trouble signal will be registered by the control panel if a short cir-
cuit does not exist across terminals 6 & 7.
4.8 UL Power-Limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at
least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit
wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the LDM-R32 is shown
+
+
+
+
-
-
-
-
TB2
TB2
EIA-485 (-)
EIA-485 (+)
4
3
2
1
TB2
4
5
6
7
3
2
1
TB1
EIA-485 IN (-)
EIA-485 OUT (-)
EIA-485 OUT (+)
EIA-485 IN (+)
N.C. Supervision
Inputs
Common In (-)
Common Out (-)
Power In (24 VDC)
Power Out (24 VDC)
Earth Ground
120W ELR
Part #71244
Host FACP
First LDM
Last LDM
Figure 4.5 Wiring Multiple LDMs - 6,000 ft. (1,800 m) max run
4
5
6
7
3
2
1
TB1
4
5
6
7
3
2
1
TB1
Device to be Supervised
Normally Closed
Trouble Contacts
Supervision
Input
Supervision
Input
5VDC @
0.5mA
When not using the Supervision input,
jumper terminals 6 & 7 together.
Figure 4.6 Wiring Supervision Terminals

Table of Contents

Related product manuals