NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022 53
Type Codes for Output Devices
The following is a list of Type Codes for SLC control module points. Select from these codes to define the type of point.
Type Code Silenceable
1
Switch
Inhibit
1
Walk Test
1
SLC Output
Point
Local
Mode
Group
Point
Types
Device Function
CONTROL
2
Y N Y NAC fire Supervised NAC
RELAY
2
Y N Y Relay n/a Relay output
BELL CIRCUIT Y N Y NAC fire Supervised NAC
STROBE CKT
2
Y N Y NAC fire Supervised NAC
HORN CIRCUIT
2
Y N Y NAC fire Supervised NAC
AUDIBLE CKT Y N Y NAC fire Supervised NAC
SPEAKER Y N Y NAC fire Supervised NAC for speaker circuits
blank
2
Y N Y NAC n/a Supervised NAC for undefined device
NONRESET CTL
2
N N N Relay or NAC n/a Supervised output, unaffected by “System Reset”
command
TELEPHONE N N N Telephone fire Supervised Telephone circuit
CONTROL NAC Y N Y NAC fire Supervised NAC
ISOLATED NAC Y N Y NAC fire Supervised NAC for notification appliance, used with
audio isolators. Activates even if there is a short on its
NAC circuit. For ULC installations only.
ISOLATED SPK Y N Y NAC fire Supervised NAC for speaker circuits, used with audio
isolators. Activates even if there is a short on its audio
circuit. For ULC installations only.
GEN ALARM
2
N Y Y NAC fire Control Module, XPC-8, or an XP5-C (in NAC mode)
configured as a Municipal Box Transmitter for NFPA 72
Auxiliary Fire Alarm Systems applications (MBT-1
required). This Type ID can also be used for general
alarm activation.
GEN SUPERVIS
2
N Y Y NAC supervisory Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any Supervisory condition (includes
sprinkler type).
GEN TROUBLE
2
N Y Y NAC trouble Control Module, XPC-8, or an XP5-C (in NAC mode)
activated under any System Trouble condition.This device
will not turn ON when it is in trouble (short or open).
GENERAL PEND
2
N Y Y NAC trouble Control Module XPC-8 circuit, or an XP5-C (in NAC
mode) that will activate upon receipt of an alarm and/or
trouble condition, and remain in the ON state until all
events have been ACKNOWLEDGED. This device will
not turn ON when it is in trouble (short or open)
TROUBLE PEND
2
N Y Y NAC trouble Control Module or an XP5-C (in NAC mode) that will
activate upon receipt of a trouble condition, and remain in
the ON state until all troubles have been
ACKNOWLEDGED. This device will not turn ON when it
is in trouble (short or open).
ALARMS PEND
2
N Y Y NAC fire Control module or NAC for output that will activate upon
receipt of an alarm condition, and remain in the alarm
state until all alarms have been acknowledged.
INST RELEASE
3
NYNNAC (SLC
only)
fire Supervised for open circuits and ground faults. Short =
normal
REL. FORM C
2,3
NYNForm-C relay
(SLC only)
n/a Directs relay outputs to perform a releasing function.
RELEASE CKT
2,3
NYNNAC (SLC
only)
n/a Directs outputs to perform a releasing
function.Supervised for open circuits and ground faults.
Short = normal
REL CKT ULC
2,3
NYNNAC (SLC
only)
n/a Directs outputs to perform a release function as required
by ULC.
REL END BELL N Y N NAC n/a Activates NAC audio or visual device when releasing
circuits shut off.
REL AUDIBLE Y Y N NAC n/a Activates audio or visual devices steady when releasing
starts.
Table 7 SLC Control Module Type Codes (1 of 2)