NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022 71
The units may employ the following features
• Alarm verification (maximum verification period of 60 seconds (30 seconds per ULC) or field programmable between 0 and 60 seconds)
• Supports standard 2-wire smoke detectors using Model FZM-1
•Walk test
• Supports addressable or analog devices
• Field Programming
• Signal Silence Inhibit
• Remote annunciator outputs
• Automatic Alarm Signal Silence
• Drift compensation
• Detector sensitivity testing per Par. 7-3.2.1 of NFPA 72
The following tables display System Configuration information for ULC applications:
UL Type Service Model IDC Class
Initiating
Device Types
NAC Type Signaling Signal Line Circuit
Local NFS2-3030
NFS2-3030E
B, D A, M, WF, SS A, B C(1), NC (Class B)
(Class A,X)
Auxiliary NFS2-3030
NFS2-3030E
B, D A, M, WF N/A N/A (Class B)
(Class A,X)
Remote Station (PPU) NFS2-3030
NFS2-3030E
B, D A, M, WF, SS N/A DACT, Rev. Pol.,OT
(1)
(Class B)
(Class A,X)
Proprietary (PPU) NFS2-3030
NFS2-3030E
B, D N/A N/A NC (Class B)
(Class A,X)
Proprietary (Rec. Unit) NFS2-3030
NFS2-3030E
B, D N/A N/A MX (Class B)
(Class A,X)
Central Station (PPU) NFS2-3030
NFS2-3030E
B, D A, M, WF, SS N/A DACT, OT
(1)
(Class B)
(Class A,X)
Proprietary (Burg) NFS2-3030
NFS2-3030E
B, D N/A N/A MX (1) (Class B)
(Class A,X)
Smoke Control NFS2-3030
NFS2-3030E
B, D A, M, WF, SS N/A N/A (Class B)
(Class A,X)
Process Management
(Non-emergency)
NFS2-3030
NFS2-3030E
B, D A, M A, B C,NC (Class B, Class A)
Emergency Signaling NFS2-3030
NFS2-3030E
B, D A, M A,B C,NC (Class B, Class A)
1. Requires separately listed equipment
Table 12 UL Type of Service Configurations
Module Description Local AUX RS P (PPU) *REL *P Rec
CPU2-3030
(CPU2-3030DC for Canada
Only)
CPU Board w/display Y Y Y Y Y Y
CPU2-3030ND CPU Board w/o display O O O O O O
LCM-320 Loop Control Module Y Y Y Y Y Y
LEM-320 Loop Extender Module O O O O O O
AMPS-24
Alternate Construction AMPS-24
Power supply Y(1) Y(1) Y(1) Y(1) Y(1) Y(1)
AMPS-24E
Alternate Construction AMPS-24E
Power Supply Y(1) Y(1) Y(1) Y(1) N Y(1)
TM-4* Transmitter Module N Y Y(2) Y O O
DVC/DVC-EM Digital Voice Command/Extended
Memory Module
OOOO O O
DAA-5025(E) * Digital Audio Amplifier O O O O O O
DAA-5070(E) * Digital Audio Amplifier O O O O O O
NCA-2/C * Network Control Annunciator O O O O O O
NCD Network Control Display O O O O O O
NCS4-W-ONYX/
NCS4-F-ONYX
Network Control Station O O O O O O
NCM-W/F* Network Control Module O O O Y O O
CAB-A4* Enclosure Y(3) Y(3) Y(3) Y(3) Y(3) Y(3)
CAB-B4* Enclosure Y(3) Y(3) Y(3) Y(3) Y(3) Y(3)
CAB-C4* Enclosure Y(3) Y(3) Y(3) Y(3) Y(3) Y(3)
Table 13 System Configuration for ULC Requirements (1 of 3)