74 NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
8 System Power/Size
9 Operating Instructions
Frame and mount the NFS2-3030 Operating Instructions #52547, adjacent to the control panel.
Power Current
Max. AH
Capacity
Derating Factor
Max. Standby
Current
Max. Alarm
Current
Max. Standby
Time
Max. Alarm
Duration
Primary
(Power
Supply)
5A (AMPS-
24 Power
Supply);
or
2.5A (AMPS-
24E Power
Supply)
N/A N/A 891 mA
(AMPS-24)
or
498 mA
(AMPS-24E)
2.4 A
(AMPS-24)
or
1.46 A
(AMPS-24E)
N/A N/A
Secondary
(backup)
7.4A 200AH 26 AH batteries: UL=1.2, ULC=1.2
55 AH batteries: UL=1.2, ULC=1.8
100 AH batteries: UL=1.2, ULC=2.5
200 AH batteries: UL=1.2, ULC=2.5
4.4A
(For 26AH
batteries: max
standby current
cannot exceed
0.65A.)
7.4A
(max alarm
current
cannot
exceed
6.75A.)
24 hours 5 minutes
standard,
15 minutes for
emergency
voice/alarm
communications
systems.
Table 15 System Power
Accessories/Subassemblies/Networked panels Maximum System Capacity
Monitor and Control Modules 159 per loop, up to 1,590 total
Detectors 159 per loop, up to 1,590 total
Signaling Line Circuits (SLC) 10
NFS2-3030 Fire Alarm Control Panel High-Speed Noti•Fire•Net - 200 Nodes
Noti•Fire•Net - 103 Nodes. 54 nodes when DVC is used in
network paging.
Table 16 System Size