Section 6. System Programming
6–47
L2: – Partition, zone configuration, supervision options
Partition Hardwire Loop Type Wireless Supervision
L2
Entry
1 2 EOL N/C N/O Supervise Tamper
0
✔ ✔ ✔ ✔
1
✔ ✔ ✔ ✔
4
✔ ✔ ✔
5
✔ ✔ ✔
8
✔ ✔ ✔
9
✔ ✔ ✔
Partition: Select the partition in which
the zone is located.
Hardwire Loop Type – If this is a
hardwire zone, select the type of loop.
This selection is not applicable for
double-balanced, fast, or zone doubling
zones. For EOL, use a 2.2k loop resistor.
Wireless Supervision – If this is a
wireless zone, select whether it will be
supervised and/or have tamper
protection active.
L3 Entry:
L3
Entry
Silent
Zone
Swinger*
0
1
✔
2
✔
Silent – If selected, alarms will be sent to the central station but no
sounding (bell, keypad sounder) will occur.
Swinger – If selected, this zone will stop reporting alarms during a
single armed period if the number of alarms within that armed period
exceeds the number set in Submode 1, Question 13, Location 4.
3
✔ ✔
* Erratic or unstable sensor
U
L
Swinger option must be disabled for UL installations.
L4 Entry:
L4
Entry Stay
Auto-
Stay Chime
Dial
Delay
0
1
✔
2
✔
3
✔ ✔
4
✔
5
✔ ✔
6
✔ ✔
7
✔ ✔ ✔
8
✔
9
✔ ✔
A
✔ ✔
B
✔ ✔ ✔
C
✔ ✔
D
✔ ✔ ✔
E
✔ ✔ ✔
F
✔ ✔ ✔ ✔
Stay – If selected, zone will be bypassed if the system is
armed in STAY mode.
Auto-Stay – If selected, zone will be automatically
bypassed if a delay zone (e.g. entry/exit door) is not faulted
during exit delay.
Chime – If selected, a fault on this zone while the system
is disarmed allows the keypad to emit a 1-second beep.
When this feature is selected, the beep may be turned on or
off by the user entering the #6 command.
Dial Delay – If selected, transmission of alarms on this
zone will be delayed by the time selected in Question 19,
Location 4.