PRO3200 Installation
Setting Up the PRO3200 Hardware
The PRO3200 DIP switches need to be set twice:
1. Configure the S4-S3-S2-S1 DIP switches to off-off-on-off to set the default TCP/IP address to
192.168.0.251.
2. Apply power to the panel to set the IP address.
3. Change the S4-S3-S2-S1 combination to off-off-off-on.(DIP switch 1 is “read on the fly”).
This sets the login to the default user ID (“admin”) and password (“password”) for Ethernet
communications.
4. Create users. See 'User Configuration' on page 25 for instructions.
5. Set the S4-S3-S2-S1 combination to off-off-off-off.
6. Configure the host port for TCP/IP and/or Serial communications. See 'Host Port' on page 20
for instructions. This will enable both TCP/IP and serial hardware networking when you log in
again.