Honeywell S4-34440-12 - Product Features; Fail-safe Operation

Honeywell S4-34440-12
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN54-17 : 2005
(section 4.8)
data:
Vmax 42V IC max 0.4A
V
nom 40V IS max 1A
V
min 24V IL max 20mA
V
SO max 16V ZC max 0.1W
V
SO min 8V
Emission BS EN61000-6-3: 2007 EMC for
residential, commercial & light
Industry.
Immunity BS EN50130-4: 1996 +
A1:1998 +A2 2003
for alarm systems
Maximum number
per loop
8 (with fully sectored outputs)
Load factor
(1000 maximum)
1
Terminals 3-way device (terminals
provided for spur or sub-loop)
&
Repetitive switching of capacitive loads
greater than 1500uF is not possible and will result
in the thermal protection circuit automatically
reducing the output voltage.
Features
¨
Fail-safe operation
A fail-safe operation is available on all sectored
outputs, if loop communications are lost for a defined
duration then the sector outputs will be turned ON.
Sector outputs will turn OFF immediately when
communication is restored.
¨
Synchronisation
Adjustable synchronisation pulses can be selected
for all sector outputs to synchronise the operation of
devices such as xenon strobes or speech sounders.
¨
Auxiliary Output
The Auxiliary output can be programmed to
automatically turn OFF when a mains failure occurs
to preserve battery capacity. The output can also be
programmed to provide a reset pulse when a fire
reset occurs.
Data and Installation S4 Mains powered interface unit
2 4188-968 issue 2_Part 1_09-10_S4 mains interface
PB2
S+ Z+ Z-S-
SECTOR / ZONE1
PB3
S+ Z+ Z-S-
SECTOR / ZONE2
PB4
S+ Z+ Z-S-
SECTOR / ZONE3
PB5
S+ Z+ Z-S-
SECTOR / ZONE4
PB1
0C LC 01
L1
02
L2
LOOP
LN
PB6
++--
AUX O/P
P3
FS6
T3.16A
CERAMIC
ANTI-SURGE
SW1-POWERUP
P7
Mains Powered
Interface Unit Mk 3
P1
DANGER
DO NOT
REMOVE
4 Backbox mounting points
T
op an
d
rear
cable entry points
Mains interface PCB
(Not all components shown)
Door lock
Terminals for Auxiliary output
and Zone/Sector circuits
Terminals for mains cable
+ mains fuse
Earth points for DIN rail modules
Backbox to door earth lead
DIN rail for optional modules
Quick reference label
Earth points for wiring
Loop terminals
Battery connector
Relay
Surge
Protection
IS Galvanic
Isolator
Metal
screen
FS8 F3.16A
QUICK
BLOW
Battery fuse
Battery ‘Power up’
push button
Batteries are fitted here
during commissioning
www.acornfiresecurity.com