DIN rail modules
Factory settings
¨
The S4 Mains powered interface channels1-4areallsetto
UNUSED.
¨
The Auxiliary output is off and is unaffected by mains failure or
fire reset.
Compatibility
The S4 Mains powered interface unit is compatible for use in
Vigilon and Nano systems having the following panel firmware.
Control Panel having card and firmware
Vigilon
Main Controller Card ³ V4.43 / V3.97
Loop Processor Card ³ V4.41 / V3.97
Vigilon Commissioning tool ³ V1.27
Nano
Main Controller ³ V2.50
Nano Commissioning tool ³ V2.x
Note a Nano loop can only accomodate S4-34440-12.
Backward Compatibility (for Vigilon loop)
An S4 Mains powered interface unit can be converted to be a
BACKWARD COMPATIBLE 34440 Mains powered interface unit
for use on a Vigilon loop. The conversion is done using a
S4 Interface programmer unit. For further information contact your
supplier.
4188-968 issue 2_Part 2_09-10_S4 mains interface 1
Commissioning information
S4 Mains powered interface
(S4-34440-02 & S4-34440-12)
by Honeywell
Mains Powered Interface
DIN Rail
Surge Protection
IS Galvanic Isolator
IS Galvanic Isolator
IS Galvanic Isolator
IS Galvanic Isolator
Surge Protection
Surge Protection
Relay
IS Galvanic Isolator
for
(
sounders
Part number: 02518-10)
MTL5021
Hazardous
area
1
2
-
Safe
area
-
11
12
IS Galvanic Isolator
for
(
detectors
Part number: 17740-20)
Pepperl+Fuchs
KFDO-CS-Ex1.51P
Hazardous
area
11+
Safe
area
12-
1+
2-
A2 21 11 A1
24 22 12 14
7
8
12
6
5
4
3
Relay (Part number: 19104-52)
A2 21 11A1
24Vdc
Contacts rated at
10A / 250VAC
Metal Screen
24 22 1214
www.acornfiresecurity.com
www.acornfiresecurity.com