UDC 1200 Start-Up Guide Rev 1
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down and pressing .
Once in select mode, press or to select the required mode. An unlock code is required to prevent
unauthorised entry to Configuration, Setup & Automatic Tuning modes.
Press or to enter the correct code number, then press to proceed.
Mode
Upper
Display
Lower
Display
Description
Default
Unlock
Codes
Operator
Optr
SLCt
SLCt
Normal instrument operation.
None
Set Up
SetP
SLCT
Tailor settings to the application.

Configuration
Conf
SLCT
Configures the instrument for use.

Product Info
Info
SLCT
Check manufacturing information.
None
Auto-Tuning
Atun
SLCT
Invoke Pre-Tune or Self-Tune.

Note: The instrument will always return automatically to Operator mode if there is no key activity for 2 minutes.
First select Configuration mode from Select mode (refer to section 2).
First select Configuration mode from Select mode (refer to section 3).
Press to scroll through the parameters, then press or to set the required value.
To accept a change must be pressed, otherwise parameter will revert to previous value.
To exit from Configuration mode, hold down and press , to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Parameters marked * are repeated in Setup Mode.
Parameter
Lower
Display
Upper
Display
Adjustment range
Default
Input Range/Type

See following table for possible codes
J T/C
Code
Input Type & Range
Code
Input Type & Range
Code
Input Type & Range
bC
B: 100 1824 ºC
L.C
L: 0.0 537.7 ºC
P24F
PtRh20% vs 40%:
32 3362 ºF
bF
B: 211 3315 ºF
L.F
L: 32.0 999.9 ºF
CC
C: 0 2320 ºC
NC
N: 0 1399 ºC
PTC
Pt100: -199 800 ºC
CF
C: 32 4208 ºF
NF
N: 32 2551 ºF
PtF
Pt100: -328 1472 ºF
JC
J: -200 1200 ºC
rC
R: 0 1759 ºC
Pt.C
Pt100: -128.8 537.7 ºC
JF
J: -328 2192 ºF
rF
R: 32 3198 ºF
Pt.F
Pt100: -199.9 999.9 ºF
j.C
J: -128.8 537.7 ºC
SC
S: 0 1762 ºC

0 20 mA DC
j.F
J: -199.9 999.9 ºF
SF
S: 32 3204 ºF

4 20 mA DC
KC
K: -240 1373 ºC
tC
T: -240 400 ºC

0 50 mV DC
KF
K: -400 2503 ºF
tF
T: -400 752 ºF

10 50 mV DC
k.C
K: -128.8 537.7 ºC
t.C
T: -128.8 400.0 ºC

0 5 V DC
K.F
K: -199.9 999.9 ºF
t.F
T: -199.9 752.0 ºF

1 5 V DC
LC
L: 0 762 ºC
P24C
PtRh20% vs 40%:
0 1850 ºC

0 10 V DC
LF
L: 32 1403 ºF

2 10 V DC
Parameter
Lower
Display
Upper
Display
Adjustment range
Default
Scale Range Upper
Limit

Scale Range Lower Limit +100 to Range Max
Range max
(Lin=1000)
Scale Range Lower
Limit

Range Min. to Scale Range Upper Limit -100
Range min
(Linear=0)
Decimal point
position

0=XXXX, 1=XXX.X, 2=XX.XX, 3=X.XXX
(non-temperature ranges only)
1
Control Type


Primary (heat) only


Primary & Secondary (heat/cool)
3. SELECT MODE
4. CONFIGURATION MODE