XI581/2 BUSWIDE OPERATOR INTERFACE ALPHABETIC REFERENCE
57 EN2B-0126 (74-3554-8)
5. Press the plus or minus keys to change operating mode to AUTO. Then press
Enter (↵) to complete the change.
RESULT: The entry in the Operating Mode field stops blinking but is still
highlighted.
6. Use the arrow keys to move to and highlight Back. Then press Enter (↵) to
complete  the selection.
RESULT: The 'Data Points' screen redisplays.
Listing Accumulated Runtime
Purpose To display accumulated runtime information (in hours).
Access Level You must have access level 3 to perform this task.
Select Data Points from Main Menu 1. At the Main Menu, use the arrow keys to move to and highlight Data Points.
Press Enter (↵) to complete the selection.
RESULT: The 'Data Points' screen appears. User Address is highlighted by
default.
Data Points
User Address Suppress Alarm
Manual Operation Add Template
Accumul. Runtime Delete Template
Type Selection Modify Template
Points in Trend Template Search
Select Hours Run Option 2. Use the arrow keys to move to and highlight Accumul. Runtime. Press Enter
(↵) to complete the selection.
RESULT: The display window lists the points and the number of hours each has
run since it was last serviced.
Accumulated Runtime
Supply fan 1267 ▲
▲▲
▲
Exhaust fan 1257 ■
Burner 476 1
Htg. zone pump 736 ■
Cafe. hood 123 ▼
NOTE: The hours run for all points may not be able to appear in the display
window at the same time.
3. Press Cancel (C) to return to the list of point description options. When you are
finished, repeatedly press Cancel (C) to return to the Main Menu.
Disabling a Point from Trend Log
Trend log memory collects and saves up to 200 of the most recent change-of-state
(COS) conditions from up to 20 trend points in a controller. A trend point is a point
that is designated (in the controller’s application program) to report changes in its
state/value to the trend log memory.
Operators can request a trend log report which extracts the trend point COS
information from the trend log memory and outputs the trend information in the
XI581/2 display window.
This function disables a point so it cannot contribute associated COS activity to the
trend log memory and it cannot appear in a trend log report output.
NOTE: To enable a point’s trending capability, see section "Selecting Points by
User Address" (page 53).