ALPHABETIC REFERENCE XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8) 60
7. Reenter the 'Suppress Alarm' option if you want to verify the change you just
made.
Press Cancel (C) to return to the Main Menu.
Assigning Distributed I/O Modules
Purpose To assign Distributed I/O modules whenever there is more than one Excel 500 con-
troller on the L
ONWORKS network.
NOTE: If there is only one Excel 500 controller on the L
ONWORKS network,
Distributed I/O modules are assigned automatically.
IMPORTANT
To perform the module assignment in this section, Distributed I/O modules
must be XFL5xxB 2.xx firmware or later.
Access Level You must have access level 3 to perform this task.
Select System Data from Main Menu 1. At the Main Menu, highlight System Data and press Enter (↵) to complete the
selection.
RESULT: The 'System Data' screen displays four possible options (depending
on access level).
System Data
System Info
HW-Interface Config.
Flash EPROM
Buswide Access
2. Use the arrow keys to move to and highlight HW-Interface. Config. Then press
Enter (↵) to complete the selection. The following screen displays.
HW-Interface Configuration
C-Bus ▲
▲▲
▲
Lon-Bus 1
B-Port ■
3. Use the arrow keys to move to and highlight LON-Bus and press Enter (↵) to
complete the selection. The 'LON-Bus' screen is displayed.
LON-Bus Configuration
Contr. Neuron ID: ACF123BDE789
Show DIO Module Assignment
Edit DIO Module Assignment BACK
The Neuron ID is the unique number assigned to the controller’s processor and
cannot be edited.
4. Use the arrow keys to move to and highlight either the Show DIO Module
Assignment or Edit DIO Module Assignment options and press Enter (↵) to
complete the selection.
RESULT: A listbox showing the Distributed I/O modules by address is
displayed. If Show DIO Module Assignment was selected, the
information is displayed only and cannot be modified. If Edit DIO
Module Assignment is selected, the following warning screen
appears before the listbox screen: