XI581/2 BUSWIDE OPERATOR INTERFACE ALPHABETIC REFERENCE
59 EN2B-0126 (74-3554-8)
Access Level You must have access level 3 to perform this task.
Select Data Point from Main Menu 1. At the Main Menu, use the arrow keys to move to and highlight Data Points.
Press Enter () to complete the selection.
RESULT: The 'Data Points' screen appears. User Address is highlighted by
default.
Data Points
User Address Suppress Alarm
Manual Operation Add Template
Accumul. Runtime Delete Template
Type Selection Modify Template
Points in Trend Template Search
Select Point Suppression Option 2. Use the arrow keys to move to and highlight Suppress Alarm and then press
Enter () to complete the selection.
RESULT: The display window lists suppressed points.
Suppress Alarm
Exhaust_fan
Hall_main_lights
Main_water_meter 1
Conf_room_temp
NOTE: All suppressed points may not be able to appear in the display
window at the same time.
Select a Point 3. Use the arrow keys to move to and highlight the point for which you want to
unsuppress alarm conditions. Press Enter () to complete the selection.
NOTE: Additional user-defined text may appear on the line beneath the user
address.
RESULT: The window allows you to unsuppress the point so it can report
alarm information.
NOTE: Regardless as to whether an alarm is suppressed or not, whenever
the alarm occurs, it is written to the alarm buffer. The difference is
that if the alarm is suppressed, it does not display on an operator
interface.
Suppress Alarm
Hall main lights
Suppress Alarm: YES
Back
4. Use the arrow keys to move to and highlight the Suppress Alarm field. Press
Enter () to complete the selection.
RESULT: The entry in the Suppress Alarm field starts blinking and is no longer
highlighted.
5. Press the plus or minus keys to change 'Suppress Alarm' between 'Yes' and
'No'. Press Enter () to complete the selection.
RESULT: The entry in the Suppress Alarm field stops blinking but is still high-
lighted.
6. Use the arrow keys to move to and highlight Back. Press Enter ().
RESULT: The 'Data Points' screen redisplays.