14 Environmental and technical specifications
Environmental and technical specifications
There are specific environmental and technical specifications for each hardare platform. The
specifications help you when planning the appropriate installation location, environmental conditions, and
resources, such as power and cooling.
Enclosure size and weights
OmniCube servers have specific size dimensions and weights. This information helps you when planning
to install the enclosure in a rack.
Dimension Centimeters Inches
Enclosure width 48.2 17.5
Maximum height 8.73 3.44
Maximum depth (from rack
flange)
75.58 29.75
The maximum weight of a system with all storage drives installed is 30.4 kg, or 67.02 lbs.
Power and thermal
OmniCube servers have two redundant power supplies with specific power and thermal specifications.
Table 5: OmniCube Power and Thermal Specifications
Specification Description
Current consumption 10A-5A
Supply voltage 100–240V AC (autoranging). Make sure each
power source has sufficient electrical overload
protection.
Frequency 50/60Hz
Heat dissipation 4100 BTU/hr max
Maximum inrush current 55A
Energy efficiency Energy Star, spec version 1.0
Power supply efficiency 90-96% efficient (load dependent)
Temperature and humidity
OmniCube servers have limits for temperature and humidity under operating and storage conditions.