47
LP-454 REV. 1.6.15
Table 14 - NOTE: If you replace a part to remedy a fault, it is recommended that you cycle the unit at least three or four times to assure the
fault has been resolved.
F13
Combustion fan speed
incorrect The heater will lock
out if it senses that the fan
speed is less than 70% of
expected rate for more than 60
seconds.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.