Power Quality Response Modes supported by the inverter can be implemented by setting
Voltage rise suppression parameters.
Power derating for voltage variation (Volt-Watt mode): The inverter power output will vary
in response to the AC grid voltage. This is switched on by default. This mode can be
enabled via the
conguration App. Please refer to the Set Q-U and P-U through
FusionSolar APP, or contact Technical Support for more information.
Reactive power regulation for voltage variation (Volt-VAr mode): The power output or input
will vary in response to the AC grid voltage. This function is switched
o by default. This
mode can be enabled via the conguration App. Please refer to the Set Q-U and P-U
through FusionSolar APP, or contact Technical Support for more information.
----End