Parameter Description Value Range
Charge from grid If Charge from grid function is
disabled by default, comply
with the grid charge
requirements stipulated in local
laws and regulations when this
function is enabled.
Disable
Enable
Grid charge cuto
SOC
Set the grid charge cuto SOC. [20%, 100%]
7.2.2 AFCI
Function
If PV modules or cables are not properly connected or damaged, electric arcs may
occur, which may cause
re. Huawei SUN2000s provide unique arc detection in
compliance with UL 1699B-2018 to ensure the safety of users' lives and property.
This function is enabled by default. The SUN2000 automatically detects arc faults.
To disable this function, log in to the FusionSolar app, enter the Device
Commissioning screen, choose Settings > Feature parameters, and disable AFCI.
Clearing Alarms
The AFCI function involves the DC arc fault alarm.
The SUN2000 has the AFCI alarm automatic clearance mechanism. If an alarm is
triggered for less than
ve times within 24 hours, the SUN2000 automatically
clears the alarm. If the alarm is triggered for
ve times or more within 24 hours,
the SUN2000 locks for protection. You need to manually clear the alarm on the
SUN2000 so that it can work properly.
You can manually clear the alarm as follows:
Method 1: FusionSolar App
Log in to the FusionSolar app and choose My > Device Commissioning. On
the Device Commissioning screen, connect and log in to the SUN2000 that
generates the AFCI alarm, tap Alarm management, and tap Clear on the
right of the DC arc fault alarm to clear the alarm.
Copy-SUN2000-(2KTL-6KTL)-L1
User Manual 7 Man-Machine Interaction
Issue 06 (2022-03-10) Copyright © Huawei Technologies Co., Ltd. 73