NO TE
Class C environment: Outdoor areas more than 500 m away from the sea. If a site
is near a pollution source, it must be 1500–3000 m away from heavy pollution
sources, such as smelteries, coal mines, and thermal power plants; 1000–2000 m
away from medium pollution sources involving chemicals, rubber, and
galvanization; or 500–1000 m away from light pollution sources, such as packing
houses, tanneries, boiler rooms, slaughterhouses,
landlls, and sewage treatment
plants.
Class D environment: Sea environments or outdoor areas within 500 m away from
the sea. If a site is near a pollution source, it is within 1500 m away from heavy
pollution sources such as smelteries, coal mines, and thermal power plants, within
1000 m away from medium pollution sources such as chemical, rubber, and
galvanization industries, or within 500 m away from light pollution sources such as
packing houses, tanneries, boiler rooms, slaughterhouses, landll sites, and sewage
treatment plants.
Class E environment: Special environments, such as underground or underwater
environments.
Mounting Structure Requirements
The device must be installed in a
reproof structure.
Do not install the Smart PCS on ammable building materials.
The Smart PCS is heavy. Ensure that the installation surface is solid enough to
bear its weight.
In residential areas, do not install the Smart PCS on gypsum boards or walls
made of similar materials which
oer weak sound insulation performance to
avoid disturbing residents.
Figure 4-1 Mounting structure
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 4 Installation
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 24