The cable colors shown in the electrical connection diagrams provided in this chapter are
for reference only. Select cables in accordance with local cable specications (green-and-
yellow cables are only used for PE). The factors that aect cable selection include the rated
current, cable type, routing mode, ambient temperature, and maximum expected line loss.
5.2 Preparing Cables
Table 5-1 Cable description (S: cross-sectional area of the AC cable conductor; S
p
: cross-sectional
area of the ground cable conductor)
Cable Type Conductor Cross-
Sectional Area
Range
Outer
Diameter
Source
DC power
cable
Prefabricated DC power
cable (with a corrugated
pipe)
50 mm
2
25 mm Delivered
with the
ESS
Ground cable
[1]
Single-core outdoor copper
cable and M10 OT/DT
terminals
S
p
 ≥ S/2 - Prepared by
the
customer
Communicatio
ns cable
FE communications cable:
CAT 5E outdoor shielded
network cable (internal
resistance ≤ 1 ohm/10 m)
and the shielded RJ45
connector
0.2-0.25 mm
2
6.5-7.1 mm The cable
delivered
with the
device is 1.2
m long. You
can also
prepare a
cable
according
to site
requirement
s.
AC power cable
(multi-core)
Three-core (L1, L2, L3)
outdoor cable and M12
OT/DT terminals (L1, L2, L3)
70–240 mm
2
30–65 mm Prepared by
the
customer
AC power cable
(single core)
Single-core outdoor cable
and M12 OT/DT terminals
70–240 mm
2
15–35 mm Prepared by
the
customer
Note [1]: The value of S
p
 is valid only if the conductors of the ground cable and AC power cable
use the same material. If the materials are dierent, ensure that the conductor of the ground
cable with a proper cross-sectional area produces a conductance equivalent to that of the cable
specied in the table. The specications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
 
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 5 Electrical Connections
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 34