6.5.4 Setting Power Adjustment Parameters
Procedure
Step 1 On the home screen, tap Power adjustment to go to the parameter setting
screen.
----End
Parameters
No. Category Parameter Description Remarks
1 Remote control Remote power
schedule
If this parameter is set to
Enable, the inverter responds to
the scheduling instruction from
the remote port. If this
parameter is set to Disable, the
inverter does not respond to the
scheduling instruction from the
remote port.
-
2 Active power Plant active power
gradient (min/%)
Species the rate of active power
rise due to sunlight changes.
-
3 Active power
change gradient
(%/s)
Species the change rate of the
device's active power.
-
4 Active power (kW) Species the xed active power
of the device.
-
5 Active power (%) Species the active power of the
device in percent.
-
6 Reactive power Reactive power
change gradient
(%/s)
Species the change rate of the
device's reactive power.
-
7 Power factor Species the power factor of the
device.
-
8 Reactive power
compensation
(Q/S)
Species the reactive power of
the device.
-
9 Q-U
characteristic
curve
Q-U characteristic
curve
The device adjusts Q/S (the ratio
of the output reactive power to
apparent power) in real time
based on U/Un(%) (the ratio of
the actual power grid voltage to
the rated power grid voltage).
-
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 6 Power-On Commissioning
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 69