No. Category Parameter Description Remarks
55 VSG inertia time
constant (s)
Species the time required for
the virtual rotor of the virtual
synchronous generator to
reach the rated speed from
the static state under the
rated torque.
56 P-F adjustment
coecient (%)
Species the frequency
deviation corresponding to
the rated active power of the
virtual synchronous generator.
57 Q-V adjustment
coecient (%)
Species the voltage
deviation corresponding to
the rated reactive power of
the virtual synchronous
generator.
58 P-V adjustment
coecient (%)
Species the voltage
deviation corresponding to
the rated active power of the
virtual synchronous generator.
59 Q-F adjustment
coecient (%)
Species the frequency
deviation corresponding to
the rated reactive power of
the virtual synchronous
generator.
60 VSG output
voltage
correction
coecient (%)
Corrects the deviation caused
by the transformer ratio error.
61 VSG output
frequency
damping
coecient (%)
Species the power factor
that prevents the frequency
change of the virtual
synchronous generator.
62 VSG excitation
time constant
(s)
Species the time required for
the excitation of the virtual
synchronous generator to
reach the rated voltage.
63 VSG excitation
damping
constant (%)
Species the power factor
that prevents the voltage
change of the virtual
synchronous generator.
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 6 Power-On Commissioning
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 68