No. Category Parameter Description Remarks
46 Delay of
underfrequency-
caused power
raising
Delay from the time when
the underfrequency-caused
power raising function is
triggered to the time when
the function takes eect
47 Output
impedance
enhancement
Output
impedance
enhancement
After Output impedance
enhancement is enabled, you
can set Frequency to which
output impedance
enhancement applies to
increase the output
impedance at this frequency.
-
48 Frequency to
which output
impedance
enhancement
applies
Species the frequency to
which output impedance
enhancement applies.
This parameter is
displayed when
Output impedance
enhancement is set
to Enable.
49 Microgrid
compatibility
Microgrid
compatibility
When Microgrid
compatibility is set to
Enable, the inverter
(including the grid-connected
current source PCS) supports
a higher ratio of PV to energy
storage in addition to the
original grid code feature of
the country.
-
50 CAN build-out
resistor
CAN build-out
resistor
Species the termination
resistors to be connected at
both ends of the CAN bus.
-
51 Working mode PQ Species the PQ working
mode in the grid-tied
scenario.
-
52 VSG Species the VSG working
mode in the o-grid scenario.
-
53 Per unit
armature
resistance (%)
Species the resistance per
unit value for armature
windings of the virtual
synchronous generator.
This parameter is
displayed when
Working mode is
set to VSG.
54 Per unit
armature
inductive
reactance (%)
Species the inductive
reactance per unit value for
armature windings of the
virtual synchronous generator.