No. Category Parameter Description Remarks
20 Reactive power
compensation
(cosφ-P) exit
voltage
Species the voltage threshold
for exiting reactive power
compensation based on the
curve.
-
21 Reactive power
adjustment time
Species the adjustment time for
the reactive power to reach the
target value during reactive
power adjustment.
-
22 Power baseline Apparent power
baseline (kVar)
Set the apparent power baseline
for power scheduling. The value
cannot be greater than the
maximum apparent power.
-
23 Active power
baseline (kVar)
Set the active power baseline for
power scheduling. The value
cannot be greater than the
maximum active power.
-
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 6 Power-On Commissioning
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 71