PDU8000 Modular Precision PDC V2.0
User Manual
7 MDU Commissioning Guide
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Main input 1 CT ratio
The value ranges from 50 to 800.
Main input 2 CT ratio
The value ranges from 50 to 800.
Br. cur. shock threshold (%)
The value ranges from 150 to 500.
x harmonic frequency
The value ranges from 2 to 63.
y harmonic frequency
The value ranges from 2 to 63.
z harmonic frequency
The value ranges from 2 to 63.
Package integrity protection
Can be set to Disable or Enable.
7.4.3.4 Branch Parameter Settings
On the Settings screen, tap Branch Param. to access the screen.
Tap Set Branch 1 Alias or Set Branch 2 Alias to set circuit breaker alias.
Tap Set Rated Current to set circuit breaker parameters.
Figure 7-35 Branch Param.
Rated Current (A)