System overvoltage (%)
Specifies the upper alarm threshold in relative to the rated voltage. The value ranges from 105
to 125.
Overvoltage ack.time (s)
Specifies the duration for confirming an overvoltage alarm. The value ranges from 1 to 10.
System undervoltage (%)
Specifies the lower alarm threshold in relative to the rated voltage. The value ranges from 75
to 95.
Undervoltage ack.time (s)
Specifies the duration for confirming an undervoltage alarm. The value ranges from 1 to 10.
Overload (%)
Specifies the overload alarm threshold in relative to the rated load. The value ranges from 100
to 120.
Overload ack.time (s)
Specifies the duration for confirming an overload alarm. The value ranges from 1 to 10.
Overfrequency (Hz)
Specifies the overfrequency alarm threshold in relative to the rated frequency. The value
ranges from 1 to 10.
Overfrequency ack.time (s)
Specifies the duration for confirming an overfrequency alarm. The value ranges from 1 to 10.
Upper load cur. thre. (%)
Specifies the upper alarm threshold in relative to the rated current. The value ranges from 80
to 100.
Lower Load cur. thre. (%)
Specifies the lower alarm threshold in relative to the rated current. The value ranges from 30
to 80.
7.4.3.6 Setting Wizard
On the Settings screen, tap Setting Wizard to access the screen.