Huawei PDU8000 Series - Replacing Monitoring Board

Huawei PDU8000 Series
157 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PDU8000 Modular Precision PDC V2.0
User Manual
8 Maintenance Guide
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
137
Fuse No.
Function
1FU15/2FU15
Voltage sampling fuse of phase L1 on the power board to the right of the
third output subrack (cabinet rear view)/Voltage sampling fuse of phase
L3 on the power board to the left of the third output subrack (cabinet rear
view)
The preceding tables use a fully configured PDC as an example. The actual cabinet configurations
prevail.
*FU*-1 indicates the fuse input end, and *FU*-2 indicates the fuse output end.
Procedure
Step 1 Push the fuse handle up outwards.
Step 2 Remove the faulty fuse.
Figure 8-17 Removing a fuse
Step 3 Install a new fuse, and reinstall the handle.
----End
8.4.6 Replacing a monitoring board
Prerequisites
Tool: Phillips screwdriver
Materials: new monitoring board