PDU8000 Modular Precision PDC V2.0
User Manual
8 Maintenance Guide
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
123
Alarm
Name
Alarm
Severity
Impact
Possible
Cause
Solutions
Branch
abnormal
Warning
A branch switch
is on, but no
current is
detected.
No loading
If you do not to display
a Branch abnormal,
you set Branch
abnormal to Custom,
and set the branch to
Disable.
MDU path: System
Info. > Setting >
System Param.
Branch
overload
Critical
The current of a
branch exceeds 1
time of the rated
current (multiple:
11.2;
confirmation
time: 110s).
The branch is
overloaded.
Check the load power
of the branch.
Max. br. cur.
exceed
Major
The current of a
branch exceeds
0.8 time of the
rated current
(multiple: 0.81).
The branch is
overloaded.
Check the load power
of the branch.
Min. br. cur.
exceed
Warning
The current of a
branch exceeds
0.6 time of the
rated current
(multiple:
0.60.8;
confirmation
time: 110s).
N/A
N/A
Main input
br. current
shock
Major
A surge current
three times
greater than the
rated current is
detected in a
branch (multiple:
1.55).
The insulation
of the branch
is abnormal.
Check the cable
insulation of the output
branch.