Table 3-13 SPD functional parameters
Provides lightening and transient voltage surge protection.
Operating temperature: -40°C to +70°C
Operating humidity: 5%-95%RH
Nominal discharge current In (8/20 µs) = 20 kA
Maximum discharge current Imax (8/20 µs) = 40 kA
Voltage protection level Up (20 kA, 8/20 μs) ≤ 1.8 kV (L-N)/≤
1.0 kV (N-PE)