2.2 Cables
YJV single-core cables are recommended. When the ambient temperature is 40°C,
the conductor operating temperature cannot exceed 90°C.
Table 2-1 Recommended cable specications
Name Recommended Specications
Equipotential cable
Electronic|Electric cable, 600 V, UL1015, 6 mm
2
, yellow/
green
Input power cable Positive and negative bus input cables:
Electronic|Electric cable, 800 V, ZA-YJV, 240 mm
2
, black,
single-core, double-insulation
Output power
cable
Electronic|Electric cable, 800 V, ZA-YJV, 70 mm
2
, black,
single-core, double-insulation
(Optional) Signal
cable
UL2464 300 V 22 AWG*1P twisted pair shielded cable
Table 2-2 Cable terminal requirements
Name
Terminal Specications
Equipotential cable
terminal
Bare crimping terminal, OT, 6 mm
2
, M8, tin plating
Input power cable
terminal
Bare crimping terminal, DT, 240 mm
2
, M16, tin plating
Output power
cable terminal
Bare crimping terminal, DT, 70 mm
2
, M12, tin plating
Signal cable
terminal
Single-cord end terminal, 0.5 mm
2
PDU8000 DC Combiner Cabinet
Quick Guide 2 Installation Preparations
Issue 02 (2022-08-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 7