PowerCube 5000 (SUN2000-150KTL-S0)
Installation Guide
9 Power-on and Commissioning
Copyright © Huawei Technologies Co., Ltd.
Path
Parameters
Setting
Volt Li Batt and others
DG Number
0/1
4. Set the System Param. 2.
Table 9-4 Setting the System Param. 2
Path
Parameters
Setting
Settings Wizard
Batt. String Qty.
Set based on site
requirements.
NOTE
Configurable range: 0 10
Battery Cell Num
Set based on site
requirements.
NOTE
Configurable range: 192 288
Single-String Cap (Ah)
Set based on site
requirements.
NOTE
Configurable range: 0 7000
Number of Cabinet's HSU
Set based on site
requirements.
NOTE
Configurable range: 1 5
System Start Min Capacity
Pct (%)
Set based on site
requirements.
NOTE
Configurable range: 0 100
For example: If battery routes 1 and 2 are respectively connected to a battery string (a
battery string consists of 192 2 V, 800 Ah batteries in series), set Single-String Rated
Capacity (Ah) to 800 and Quantity of Battery String to 2.
5. Set the System Param. 3.
Table 9-5 Setting the System Param. 3
Path
Parameters
Setting
Settings Wizard
Output Volt Level (V)
Set based on site requirements.
NOTE
Configurable level: 380/400/415
Output Volt Adjust (V)
Set based on site requirements.