Copyright © Huawei Technologies Co., Ltd.
Alarm ID
(Alarm
ID-Alarm
Cause ID)
connected 2# battery
control unit is faulty.
3. Replace the battery control
unit or the signal transfer
board.
The software and hardware
versions of a battery module
do not match.
Load the battery module
software.
The software and hardware
versions of the battery
control unit do not match.
The number of battery
modules is set incorrectly.
Check the number of battery
modules.
Batt.cabinet
quantity
mismatch
The configured number of
battery cabinets does not
match the actual available
number.
1. Set the number of battery
cabinets to be the same as
the actual number.
2. Check the parallel cable
connection.
Battery module
not detected
The battery control unit
does not receive an online
query response from the
battery module.
1. Check whether the signal
terminal of the battery
module is properly
connected.
2. Replace the battery
module.
The lithium battery works
abnormally and may catch
fire.
1. Check whether the alarm
is true.
2. If it is a false alarm,
manually clear it.
3. If smoke is generated,
press the EPO button to
shut down the entire
system and start the fire
extinguishing facility.
The QF2 trip unit
auxiliary contact is off.
The QF2 trip unit cannot
be disengaged.
1. Detect the QF2 auxiliary
contact wiring
2. Replace the QF2 trip unit.
Water has entered the
battery cabinet.
1. Check that the water
sensor cable is properly
connected.
2. Check the status of the
battery cabinet.