PowerCube 5000
User Manual (SmartLi 100Ah)
Copyright © Huawei Technologies Co., Ltd.
The battery low
voltage disconnection
(BLVD) and load low
voltage disconnection
(LLVD) voltage do
not exceed the
threshold.
Refer to the device
troubleshooting instructions.
The indicators are
normal and no alarm
is generated.
The insulation
layer does not
crack or
deteriorate.
The wiring
terminals are not
rusty or
disconnected.
Replace power cables.
Replace wiring terminals.
7.3 SmartLi Routine Maintenance
Before installing batteries, pay attention to safety precautions and connection methods
provided by battery manufacture.
Insulate tools used for battery maintenance.
Keep the battery switch off when installing or maintaining the batteries.
Before installing or maintaining a battery module, remove the battery management
module and reinstall it after the operation is complete.
Handle batteries gently and ensure personal safety.
Do not use any organic solvent to clean batteries.
Do not smoke or use open flames around batteries.
After batteries are discharged, charge the batteries in time to avoid affecting their service
life.
Only qualified personnel are allowed to perform maintenance.
Table 7-3 Routine maintenance
Check whether batteries are far away from heat sources and are not
exposed to direct sunlight.
If a battery experiences damage, leakage, or deformity, disconnect the
faulty battery, take photos, and then replace it.