8.1.7 Circuit Breaker Troubleshooting
Table 8-7 Troubleshooting
A circuit breaker is faulty
due to overcurrent or a short
circuit.
The circuit breaker is in a
position between ON and
OFF.
Switch the circuit breaker to
OFF and then to ON.
The circuit breaker remains
faulty after you switch it to
OFF and then to ON.
The circuit breaker is
damaged.
Replace the circuit breaker.
8.1.8 Clearing the EPO State
Table 8-8 Clearing the EPO state
The EPO button has been pressed, and the
SMU is energized.
1. Restore the EPO button.
2. Manually clear the alarm.
The EPO button has been pressed, the SMU
is not energized, and the AC input or PV
input is energized.
1. Restore the EPO button.
2. Turn off the AC and PV input switches
to power off the system.
3. Turn on the AC and PV input switches
to power on the system.
8.2 Lithium Battery Cabinet Troubleshooting
Do not clear an alarm by reseating an ESM.
Table 8-9 Troubleshooting
The indicator is
steady red.
Handle the alarm
according to the
alarm reference.
Electrochemical cell fault
The battery cabinet has
generated a critical alarm.
Handle the alarm
according to the
alarm reference.