PowerCube 5000
User Manual (SmartLi 100Ah)
C EMC
Copyright © Huawei Technologies Co., Ltd.
165
C EMC
This is a class A product. In a living environment, this product may cause radio interference.
Therefore, users may be required to take appropriate measures.
Table C-1 EMC of the ICC cabinet
Item
Specifications
Electromagnetic
interference (EMI)
Conducted emission (CE)
CISRP11-2009 Class A
Radiated emission (RE)
CISRP11-2009 Class A
Harmonic current
IEC 61000-3-2
Voltage fluctuation and
flicker
IEC 61000-3-3
Electromagnetic
susceptibility (EMS)
Electrostatic discharge
(ESD)
IEC61000-4-2, criterion B
Contact discharge: 6 kV; air
discharge: 8 kV
Electrical fast transient
(EFT)
IEC 61000-4-4 (criterion B)
Signal port: 2 kV; AC power port: 2
kV; DC power port: 2 kV
Radiated susceptibility (RS)
IEC 61000-4-3
10 V/m
Conducted susceptibility
(CS)
IEC 61000-4-6
Power port: 10 V
Surge susceptibility
IEC 61000-4-5 (criterion B)
Dry contact output: 0.5 kV in
differential mode, 1 kV in common
mode
Signal and control ports: 2 kV or
250 A
Lightning protection
PV input: 5 kA
System output: level A surge
protection; In: 60 kA; Imax: 100 kA