Cable Appearance Connector Type Cable Cross-
Sectional Area
Remarks
● One end: PP45 terminal
(connected to the
battery module)
● The other end: OT-10
mm
2
-M4-90° bent
terminal (connected to
the UPS2000-H-6KRTL-
L)
2 x 12 AWG Used to connect
battery modules
to the UPS2000-
H-6KRTL-L. The
BOM number of
the cable is
04153963, which
needs to be
purchased
separately.
● One end: PP45 terminal
(connected to the
battery module)
● The other end: OT-16
mm
2
-M6-90° bent
terminal (connected to
the UPS2000-
H-10KRTL-L)
2 x 10 AWG Used to connect
battery modules
to the UPS2000-
H-10KRTL-L. The
BOM number of
the cable is
04153964, which
needs to be
purchased
separately.
● One end: PP45 terminal
(connected to the
battery module)
● The other end: OT-16
mm
2
-M6-90° bent
terminal (connected to
the UPS2000-
G-15KRTL-01 or
UPS2000-G-20KRTL-01)
2 x 10 AWG Used to connect
battery modules
to the UPS2000-
G-15KRTL-01 or
UPS2000-
G-20KRTL-01. The
BOM number of
the cable is
04151503, which
needs to be
purchased
separately.
● One end: OT-6 mm
2
-
M6-90° bent terminal
(connected to the BBB
box)
● The other end: OT-6
mm
2
-M4-90° bent
terminal (connected to
the UPS2000-H-6KRTL-
L)
6 mm
2
Used to connect
the BBB box to
the UPS2000-
H-6KRTL-L. Onsite
preparation is
required.
SmartLi-ESM-24020P1
Quick Guide 1 Installation and Cable Connection
Issue 03 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 6