● After batteries are discharged, they cannot enter the charging state due to a
system fault.
● Batteries are not charged immediately after EOD.
Table 2-1 Mappings between SOC ranges and charging intervals
SOC Range Maximum Charging Interval
SOC ≥ 30% 90 days
20% ≤ SOC <30% 75 days
10% ≤ SOC < 20% 60 days
5% ≤ SOC <10% 30 days
SOC < 5% 20 days
SmartLi-ESM-24020P1
Quick Guide 2 Power-On Commissioning
Issue 03 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 62