M6 (4 PCS)
4 N·m
9. Connect the wires of the AC output cable for the SUN2000-33KTL to L1, L2, L3, and N on the
AC terminal block. The required torque is 4 N·m. Connect the wires of the AC output cable for
the SUN2000-40KTL to L1, L2, and L3 on the AC terminal block. The required torque is 8 N·m.
10.Use a torque wrench to tighten the locking cap to a torque of 7.5 N·m.
Ensure that the AC output power cable is securely connected. Otherwise, the inverter may fail to
run or the terminal block may be damaged after the inverter operates.
5
M8 (3 PCS)
8 N·m
a. SUN2000-33KTL b. SUN2000-40KTL
Positive and negative metal terminals
Optional DC input terminals
Negative metal terminal (male)
Positive metal terminal (female)
Connects to any one route
Connects to routes 1 and 3
Connects to routes 1, 3, and 5
Connects to routes 1, 2, 3, and 5
Connects to routes 1, 2, 3, 4, and 5
Connects to routes 1, 2, 3, 4, 5, and 6
Routes 1, 2, 3, 4, 5, and 6 are defined
from left to right.
Installing DC Input Power Cables
2.3