EasyManua.ls Logo

Huawei SUN2000-33KTL - Electrical Connection; Installing a PGND Cable; Installing AC Output Power Cables

Huawei SUN2000-33KTL
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
Inverter Model
Cable Type
Cross-sectional Area of the
Cable (Recommended)
SUN2000-33KTL
4-core outdoor cable (L1, L2, L3, N)
16 mm
2
or 6 AWG
SUN2000-40KTL
3-core outdoor cable (L1, L2, L3)
The table lists only the recommended cable specifications. For more information about cable
specifications, see the SUN2000-(33KTL, 40KTL) User Manual.
2
Electrical Connection
M6 (1 PCS)
5 N·m
1. Remove the two screws from the chassis door using a hex key and set them aside.
1. Do not open the door on the upper side of
the inverter.
2. Before opening the chassis door, switch off
the upstream DC input circuit breaker and
downstream AC output circuit breaker.
OT-M6
Installing a PGND Cable
2.1
OT-M6
Installing AC Output Power Cables
2.2
OT-M6
PE terminal
1. It is recommended that an 8 mm
2
or 8 AWG
outdoor copper-core cable be used as a ground
cable. Ground cables must be securely
connected.
2. It is recommended that the ground cable be
connected to a nearby ground position. For a
system with multiple inverters connected in
parallel, connect the ground points of all
inverters to ensure equipotential connections.
3. To prevent corrosion, apply silica gel or paint to
the PE terminal after connecting the PGND
cable.
NOTE
NOTE
NOTICE

Other manuals for Huawei SUN2000-33KTL

Related product manuals