(1) Cable (2) Core wire (3) Heat shrink tubing
(4) OT terminal (5) Hydraulic pliers (6) Heat gun
Step 2 Connect the PE cable.
Figure 5-3 Connecting the PE cable
----End
5.4 Connecting an AC Output Power Cable
Precautions
An AC switch should be installed on the AC side of the inverter. To ensure that the
inverter can safely disconnect itself from the power grid when an exception occurs,
select a proper overcurrent protection device in compliance with local power
distribution regulations.
WARNING
Do not connect loads between an inverter and an AC switch that directly
connects to the inverter. Otherwise, the switch may trip by mistake.
If an AC switch is used with specications beyond local standards, regulations,
or the Company's recommendations, the switch may fail to turn o in a timely
manner in case of exceptions, causing serious faults.
CA UTION
Each inverter shall be equipped with an AC output switch. Multiple inverters shall
not connect to the same AC switch.
The inverter is installed with an integrated monitoring unit for residual current.
When the inverter detects that residual current exceeds the permitted value, it
disconnects from the power grid quickly.
SUN2000-(8K, 10K)-LC0 Series
User Manual 5 Electrical Connections
Issue 01 (2023-09-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 44

Table of Contents

Other manuals for Huawei SUN2000-8K-LC0 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-8K-LC0 Series and is the answer not in the manual?

Huawei SUN2000-8K-LC0 Series Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-8K-LC0 Series
CategoryInverter
LanguageEnglish

Related product manuals