NO TE
The power meter and the Smart Dongle must be connected to the same inverter.
In the preceding networking, the inverters are cascaded and support the grid-tied
point control function to achieve zero export.
If the inverters require the grid-tied point control function, they need to be
connected to a power meter.
EMMA networking
Figure 5-15 EMMA networking (the component in the dashed box is
optional)
Requirements for Signal Cables
NO TICE
Ensure that the protection layer of the cable is in the connector. The surplus
core should be cut o from the protection layer.
Ensure that the exposed core is totally inserted into the cable hole.
Ensure that the signal cables are connected securely.
Ensure that the cables are not twisted.
If multiple signal cables need to be connected to a single connector, ensure
that the outer diameters of the signal cables are the same.
Figure 5-16 Crimping two signal cables
SUN2000-(8K, 10K)-LC0 Series
User Manual 5 Electrical Connections
Issue 01 (2023-09-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 56