SUN2000 (8KTL-28KTL)
User Manual
8 Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
117
Alarm ID
Name
Severity
Causes
Measures
305
Frequency
Abnormal
Major
The actual frequency of the
grid is higher than or lower
than the required value for the
local grid.
a. If the alarm occurs accidentally,
it is possible that there is an
accidental grid abnormality. The
SUN2000 automatically reverts
to normal operating status after
the fault is rectified.
b. If the alarm occurs repeatedly,
check whether the grid frequency
is within the allowed range. If
yes, change the grid
overfrequency and
underfrequency protection points
after obtaining approval from the
local power operator. For details
about how to change the
protection points, see 7.2.9
Setting Protection Parameters. If
the grid frequency is not within
the allowed range, contact the
local power operator.
313
Low Array
Insulation
Resistance
Major
The insulation resistance
against ground of the PV
strings is low. The possible
causes are as follows:
There is a short circuit
between PV strings and the
ground.
The PV strings are installed
in a permanently moist
environment.
a. Check the insulation resistance
against the ground of the PV
strings. If there is a short circuit,
rectify the fault.
b. If the insulation resistance
against the ground is less than the
default value in a rainy
environment, set the ISO value.
For details, see 7.2.9 Setting
Protection Parameters.
318
Residual
Current
Abnormal
Major
The insulation resistance
against ground of the input
side of the SUN2000
decreases during operation,
which causes excessively high
residual current.
a. If the alarm occurs accidentally,
it is possible that there is an
accidental external circuit
abnormality. The SUN2000
automatically reverts to normal
operating status after the fault is
rectified.
b. If the alarm occurs repeatedly or
lasts a long time, check whether
the insulation resistance against
ground of PV strings is too low.
321
Cabinet
Over-Tem
p
Major
The SUN2000 is installed
in a place with poor
ventilation.
The ambient temperature is
too high.
The internal fan is not
working.
Check whether the ambient
temperature for the SUN2000
exceeds the upper limit. If so,
improve ventilation to decrease the
temperature.

Table of Contents

Other manuals for Huawei SUN2000-8KTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-8KTL and is the answer not in the manual?

Huawei SUN2000-8KTL Specifications

General IconGeneral
Max. efficiency98.6%
European efficiency98.3%
Max. DC voltage1100 V
Nominal AC output power8000 W
Weight25 kg
Operating temperature range-25°C to +60°C
Protection ratingIP65
Max. apparent AC power8800 VA
AC grid frequency50 Hz / 60 Hz
Starting voltage200 V
Number of MPPTs2
CoolingNatural convection
Maximum DC Input Power12000 W
Output Frequency50 Hz / 60 Hz
Nominal AC voltage230 V
Operating voltage range200 V - 1000 V
Rated Output Voltage230 V
MPPT Voltage Range260 V - 850 V