The AFCI function works only with Huawei optimizers or ordinary PV modules, but does not
support third-party optimizers or intelligent PV modules.
Clearing Alarms
The AFCI function involves the DC arc fault alarm.
The SUN2000 has the AFCI alarm automatic clearance mechanism. If an alarm is
triggered for less than
ve times within 24 hours, the SUN2000 automatically
clears the alarm. If the alarm is triggered for
ve times or more within 24 hours,
the SUN2000 locks for protection. You need to manually clear the alarm on the
SUN2000 so that it can work properly.
You can manually clear the alarm as follows:
● Method 1: FusionSolar App
Log in to the FusionSolar App and choose Me > Device commissioning. On
the Device commissioning screen, connect and log in to the SUN2000 that
generates the AFCI alarm, tap Alarm management, and tap Clear on the
right of the DC arc fault alarm to clear the alarm.
Figure 7-9 Alarm management
● Method 2: FusionSolar Smart PV Management System
Log in to the FusionSolar Smart PV Management System using a non-owner
account, choose Maintenance > Alarm Management, select the DC arc fault
alarm, and click Clear to clear the alarm.
Figure 7-10 Clearing alarms
SUN2000-(12KTL-25KTL)-M5 Series
User Manual 7 Man-Machine Interactions
Issue 03 (2023-02-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 63